194 Ethernet/IP (Ethernet/Industrial Protocol)
Object model
WAGO-I/O-SYSTEM 750
ETHERNET TCP/IP
7.3.2.32 Input fieldbus variable UDINT Offset (AB
hex
)
Same as the Input Fieldbus Variable UDINT (AA
hex
), however it has an offset
of 2 bytes.
7.3.2.33 Output fieldbus variable UDINT (AC
hex
)
Class
Attribute ID Access Name Data type Description Default value
1 Get Revision UINT Revision of this object 1 (0x0001)
2 Get Max Instance UINT Max. number of instances 128 (0x080)
Instance 1..128 (1. to 128. Output variable)
Attribute ID Access Name Data type Description Default value
1 Get Fb_Out_Var UDINT
Fieldbus output variable
of the PLC
0
Common Services
Service available
Service code
Class Instance
Service Name Description
0E hex yes yes Get_Attribute_Single Supplies contents of the appropriate attribute
7.3.2.34 Output fieldbus variable UDINT Offset (AD
hex
)
Same as the Output fieldbus Variable UDINT (AC
hex
), however with an offset
of 2 bytes.